+90 542 574 16 77 info@senamed.com.tr Aerocom distributor in Türkiye
Product Catalogues Exporting to 70+ countries TR EN
AREA CONTROL UNITS · 01

AURIX Area Control Panel

Steel body · 1–6 gas lines · with or without alarm

The unit consolidates medical gas lines from wards, corridors, and operating areas into a single control panel, providing both monitoring and isolation functions. Each line is equipped with a dedicated manometer, low-pressure sensor, and medical gas shut-off valve. It can be configured with or without alarms according to project requirements. Its windowed design allows all indicators and alarms to be viewed at a glance. Compatible with both recessed and surface mounting, it easily adapts to different architectural projects. Optional emergency power input can be added. Supports 1–6 gas lines, with project-specific gas combinations available. Constructed from DKP sheet and brass monoblock, the unit ensures long-lasting performance.

1–6 LINES
EN ISO 13485EN ISO 7396-1Made in Gebze, Türkiye
ABOUT THE PRODUCT

Supports 1–6 gas lines; panel width increases with the number of lines. Each line includes manometer and pressure sensor for continuous monitoring. Data can be sent to the Building Management System (BMS) for central monitoring.

KEY FEATURES

  • Gas Lines — 1–6 Gas Lines, Project-Specific Setup
  • Line Isolation — Each line can be isolated individually
  • Instant Emergency Supply — Maintains continuous gas flow
  • Installation Flexibility — Flush or Surface Mounting
  • Access Protection — Lock prevents unauthorized entry
  • Alarm Options — Touch Panel / Digital / No Alarm

TECHNICAL SPECIFICATIONS

GENERAL FEATURES
Supply Voltage
220 V, 50 Hz.
Operating Temperature
0°C – 40°C
Relative Humidity
10 – 95 %
Number of Lines (Max.)
1 – 6 Lines
Medical Gases
O₂ – N₂O – MA4 – SA7 – VAC – CO₂ – N₂
Configuration
Number of lines and gas combination are project-specific
Max. Inlet Pressure
10 Bar
Operating Pressure
0 – 8.5 Bar (Compressed Gas) 0–(-1) Bar (Vacuum)
Pressure Sensitivity
0.1 Bar
Inlet/Outlet Pipes
Top Entry, Medical Copper Pipe
Pipe Diameter
Ø15 mm (Pressure Lines) Ø22 mm (Vacuum Line)
Pressure Gauges
0–10 Bar
Vacuum Gauge
0–(-1) Bar
Emergency Supply
Gas-specific NIST connections (Project-specific gas outlet option)
Line Control
Ball Valve
Monitoring
Pressure Gauge –
MECHANICAL FEATURES
Material
CR Steel / RAL 9010 Electrostatic Powder Coated
Installation
Flush Mounted / Surface Mounted
Recommended Installation Height
1550 – 1650 mm from Floor Level (Panel Center)
Dimensions (H×W×D)
128 × 178 × 68 mm
Control
Microprocessor Controlled Electronic System
Digital Alarm Display
7-Segment Digital Display
Touchscreen Alarm Display
5" Touchscreen Display
Sensor Type
Pressure and Vacuum
Alarm Function
High/Low Pressure Alarm, Empty Gas Cylinder, Intermediate Pressure Alarm, System Changeover Alarm
Alarm Notification
Audible and Visual Warning + Notification to Master Alarm Panel
STANDARDS
Management Standards
2007/42/EC
Quality Management System
EN ISO 13485:2016 — EN ISO 9001:2015
Electrical Safety and Performance
EN 60601-1:2009 — EN 60601-1-2:2011 — EN 60601-1-8:2008
Risk, Usability and Labeling
EN ISO 14971 :2012 — IEC62366-1:2015 EN ISO 15223-1:2016 — EN 1041+A1:2011

Technical specifications are subject to change without notice. For technical drawings, model codes and all configurations, see the product catalogue (PDF) .

PROJECT CONSULTATION